2DASBOX 4input-2output Analogue-Addressable Module for 2 Doors Control

• Analogue addressable module for 2 doors control equipped with 4 balanced inputs and 2 independent outputs to receive signals from devices or detectors for the control of 2 fire door or 2 fire shutters and to control their closure with its relay output
• Each control relay output is associated with a single input which manages the closed door status
• Unit address is set via rotary switch
• 3-terminal C-NC-NO bistable relay outputs (2A at DC30V)
• Equipped with line isolator
• Dimensions W129 x H80 x D20mm
• Housed in a small plastic box
• Power consumption 5mA (quiescent status), 10mA (alarm mode)
• Power supply DC24V supplied by loop
• CPR 305/2011, EN54-17, EN54-18 certification (CPD 89/106/CEE ex certification)