NF1004 Conventional Fire Alarm Control Panel, 4 zones

• 4 zones for detectors or call points connection each composed of:
• 1 input for conventional absorption detectors with 4K7 ohm balancing resistance
• 1 line configurable:
• Open collector output
• Pull-up input for connection to a opencollector output device
• Balanced input
• 4 – 20mA input
• 1 additional zone absorption detectors/call points with 4K7 ohm balanced resistance
• 1 balanced programmable output for alarm PTC protected
• 1 RELAY NO/C/NC output for “general fault”
• 1 RELAY NO/C/NC output for pre alarm
• 2 RELAY NO/C/NC outputs configurables
• Built-in buzzer for alarm, pre-alarm and fault
• 1 DC24V output for external loads, PTC protected
• 1 resettable DC24V output for external loads, PTC protected
• Power supply system with battery charge control and loss charge
• Internal power supply unit mod. AL2SW24 – 29VDC / 2A
• Allows to connect a second power supply unit mod. AL2SW24 to double the current (optional)
• User interface with multicolor backlit graphic display, keypad and LEDs
• RS485 line for the connection of 2 NFREPEATER remote keypads (optional) and, soon available, for the connection of up to 2 C1124EN supervised
power supply (optional)
• Suitable for connection of:
• Internal extinguishing module mod. EXTING (optional)
• ETHERNET board mod. MDLAN (optional)
• GSM MODULE mod. MDGSME (optional)
• Relay board NFREL24 (optional)
• 1 USB connector
• Clock for events storing ( storage of up to 2000 single events)
• Optional batteries NTC1 and NTC2 temperature control
• Batteries 2x12V/7A internally located
• Power supply AC230V
• Power conumption 40mA (quiescent mode)
• Dimensions W320 x H304 x D83mm
• Certified CPR 305/2011 (ex CPD 89/106/EEC certification) EN 54-2, EN 54-4, EN12094-1 (with optional EXTING extinguishing module), EN 54-21
(with optional MDGSME GSM module)